MT408 - AC-Current Transducer

PDF
MT408.jpgMT408.jpg
Description

Properties

  • Sinusoidal AC current measurements
  • Current range measurements up to 6 A
  • Galvanic insulation between input and output
  • Accuracy class 0.5
  • Self powered
  • Housing for DIN rail mounting

 

Application

MT408 is intended for measuring and monitoring singlephase electrical power network. Current input is electrically insulated from the system by means of current transformer. The signal is rectified, smoothed and amplified into a DC current output.

 

The MT408 current transducer is used for a permanent monitoring of a single-phase current value. PLCs, PCs, microprocessor control, indicators, alarms units etc. can be operated by the output signal. Current input can be connected either directly to low-voltage network or shall be connected to network via a corresponding current transformer (with standard 1 A or 5 A output).

 

Technical Data

 

Input   Output
Standard nominal input current (IN)

1A, 5 A or 6 A

Measuring range limit values

0 ... 0.5 A to 0 ... 6 A

Overload capacity:

acc. to EN 60688

Max. measured value (cont.) 1,2 × IN 
Max. allowed value 2 × IN ; 1 s, 10 times, 10s interval
Nominal frequency (fN) 50, 60 Hz
Measuring frequency range 46...65 Hz
Consumption < 2 VA

 

 
Standard ranges IAN:
  • 0 … 1 mA,
  • 0 … 5 mA,
  • 0 … 10 mA,
  • 0 … 20 mA
Burden voltage:  10 V
External resistance: RB max =10 V / IAN
Maximal output voltage
(open circuit current output)
< 25 V
Maximal output current 2 × IAN
Residual ripple < 1 % p.p.
Response time < 300 ms
   

The output may be either short or open-circuited. It is electrically insulated from all other circuits

 

 

Standard nominal input current (IN)

 1A, 5 A or 6 A

Measuring range limit values

0 ... 0.5 A to 0 ... 6 A

Overload capacity:

acc. to EN 60688

Max. measured value (cont.)

1,2 × IN

Max. allowed value

20 × IN ; 1 s, 10 times, 300s interval

Nominal frequency (fN)

50, 60 Hz

Measuring frequency range

45 … 65 Hz

Consumption

< 2 VA

 

Messgröße (UN) Anzahl der Messungen Dauer einer Messung Pause zwischen zwei Messungen
1.2 x IN - dauernd -
2 x IN 5 1 s 300 s

 

Analog Ausgang

  • Stromausgang, IOutN (Ausgangsbereichsendwert):
    Bereichswerte: 0…5 mA, 0…10 mA oder 0…20 mA
  • Bürdenspannung: 15 V
  • Einstellzeit: < 300 ms
  • Restwelligkeit: < 1 % p.p.

 

Download

Liste I1

 

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.