Logo

[EQ/PQ/PQF]Ce - Meters with limit contact

PDF
eqce-pqce-fqce.jpgeqce-pqce-fqce.jpg
Description

Description

The instrument has two built-in relays with change-over contacts that are used to monitor limit values. The switching thresholds of the relays can be set with potentiometers on the front in the range of 0%...100% of the measuring range end value.

 

Versions
EQC: for alternating current/alternating voltage
PQC: for direct current/direct voltage

 

General
Supply voltage: 230VAC, +/-15% at 45-65Hz (24VDC, 110VDC, 6-30V AC/DC or 36-265 V AC/DC, optionally available)
Mounting depth: 70mm

 

Relay
Limit setting at the front over the full scale range, by screwdriver
Channel I output: Min contact
Channel II output: Max contact

Technical Data

Measurement ranges:

AC - Voltage (EQC) 0-6...600 V
AC - Current (EQC)

0-40mA...60 A

DC - Voltage (PQC)

0-25 mV...600 V

DC - Current (PQC) 0-100 µA,...25A

 EQCe 96 EQCe96 PQCe 96 PQCe96 PQFCe 96 PQFCe96


Signal adjustment
Adjustment by means of screwdriver on front side

Downloads

de-Datenblatt-EQC-PQC.pdf

 

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.