MT416 - Programmable AC-Voltage Transducer

PDF
MT416.jpgMT416.jpg
Description

Description

MT416 Programmable AC Voltage Transducer

Properties

  • Measurements of RMS voltage, frequency and THD U
  • Accuracy class 0.5 (EN 60688)
  • Input frequency range: 50/60 Hz, 400 Hz
  • RS 232/RS 485 communication up to 115, 200 bit/s and USB 2.0 communication
  • MODBUS communication protocol
  • Universal power supply or transformer power supply
  • Automatic range (max. 600 VL-N)
  • Housing for DIN rail mounting
  • User-friendly PC MiQen software

Application

MT416 is intended for measuring and monitoring single-phase voltage or frequency. Voltage input is electrically isolated from the system by means of voltage transformer. It measures RMS voltage value by means of fast sampling of voltage signals, which makes instruments suitable for acquisition of transient events. A built-in microcontroller calculates measurands (voltage, frequency, THD U, MD) from the measured signals. Measurands (U, f) can be then converted into load independent DC current or voltage which is proportional to the RMS measured value for the purpose of regulation of analogue and/or digital devices.

 

The MT416 programmable AC voltage transducer is used for a permanent monitoring of a single-phase voltage and frequency values. MT416 is delivered configured to default values. Subsequent customer configuration is possible with user friendly setting software MiQen. MT416 supports standard serial RS232/485 with speed up to 115200 bps. USB 2.0 can be used for a fast set-up or memory acquisition (after installation USB connection is not possible any more). Additional USB 2.0 interface can only be used for a fast set-up without need for auxiliary power supply. This interface is NOT galvanically isolated from analogue output and can be used ONLY unconnected to aux. supply and measuring inputs.

Techincal Data

Input   Output
Standard nominal input voltage (UN)

(see above)

Measuring range limit values

0 ... 50 V to 0 ... 500 V

Overload capacity:

acc. to EN 60688

Max. measured value (cont.) 1,2 × UN 
Max. allowed value 2 × UN ; 1 s, 10 times, 10s interval
Nominal frequency (fN) 50, 60 Hz
Measuring frequency range fN ± 10%
Consumption < 2 VA

 

 

Analogue output is fully programmable and can be set to any of 6 hardware ranges, 4 current and 2 voltage, without opening an instrument. They all use the  same output terminals.

 

Programmable DC current output:

Output range 0 … 100%

0 … 1 mA,
0 … 5 mA,
0 … 10 mA,
0 … 20 mA

other ranges possible

 

Range 1
Range 2
Range 3
Range 4

by MiQen software

Burden voltage:  10 V
External resistance: RB max =10 V / IoutN
Maximal output voltage (open circuit current output) < 25 V
Maximal output current 2 × IAN
Residual ripple < 1 % p.p.
Response time < 300 ms

 

Programmable DC voltage output:

Outputrange 0 … 100%

0 … 1 V
0 … 10 V

other ranges possible

 

Range 1
Range 2

by MiQen software

max. burden current:  20 mA
min. external resistance: RB min =Uout / 10mA
Maximal output voltage (open circuit current output) < 25 V

 

 

 

 

Download

 

We use cookies on our website. Some of them are essential for the operation of the site, while others help us to improve this site and the user experience (tracking cookies). You can decide for yourself whether you want to allow cookies or not. Please note that if you reject them, you may not be able to use all the functionalities of the site.