MT 416 - Programmable AC voltage transducer

Hauptbild - MT 416 - Programmable AC voltage transducer
Properties
  • Measurements of rms voltage, frequency, distortion factor and maximum values

  • Accuracy class 0.5 (EN 60688)

  • Input frequency ranges: 50/60 Hz, 400 Hz

  • RS232/RS485 interface (optional) with up to 115200 bit/s and USB 2.0 interface

  • MODBUS protocol

  • Auxiliary power supply via internal transformer or universal AC/DC module

  • Automatische Bereichswahl für Spannungsmessung (max. 600 VL-N)

  • Housing for DIN rail mounting

  • User-friendly MiQen software

Description

The MT416 is intended for measuring and monitoring single-phase voltages and frequencies. The voltage input is electrically isolated from the system by the use of a voltage transformer. The fast sampling of voltage signals determines the RMS value and enables the detection of fast transients. A built-in microcontroller system calculates the measured values (voltage, frequency, THD) from the measured signals. The measured values can then be converted into a load-independent DC current or voltage, which are proportional to the input variable and can be used for control purposes with analog and/or digital devices. The MT416 programmable voltage transducer is used for continuous monitoring of single-phase voltages and frequencies. The MT416 is normally programmed according to the customer's requirements. However, the end customer can also do this himself using the MiQen setting software. Serial data transmission is possible via an RS232 or an RS485 interface up to a maximum transmission speed of 115200 baud. The integrated USB 2.0 interface can be used for fast setting. After installation of the MT 416, the USB interface is no longer accessible.

Technical Data

Input

Measuring input

Nominal values

62,5, 125, 250, 500 VL-N

Nominal voltage UN

500 VL-N

Max. value (continuous)

600 VL-N

Max. Permissible value
(according to EN 60688)

2 × UN; 10 s

Input resistance

500 kOhm

Consumption

U2/500 kOhm

Frequenzmessung

Frequency measuring range
(only for frequency measurements)

16 ... 400 Hz

Output

The analogue output is fully programmable and can be set to one of the 6 ranges (4 current and 2 voltage ranges) without opening the unit.

Programmable DC current output

Programmable DC current output:
Output ranges 0 ... 100%

0 ... 1 mA

Range 1

0 ... 5 mA

Range 2

0 ... 10 mA

Range 3

0/4 ... 20 mA

Range 4

Other ranges

via MiQen software

Max. Voltage level

10 V

Maximum load resistance

RB max =10 V / IoutN

Programmable DC voltage output

Output ranges 0 ... 100%

0 ... 1 V

Range 1

0 ... 10 V

Range 2

Other ranges

via MiQen software

Max. load current

20 mA

Min. load resistance

RBmin= UoutN / 10 mA