Measurements of rms voltage, frequency, distortion factor and maximum values
Accuracy class 0.5 (EN 60688)
Input frequency ranges: 50/60 Hz, 400 Hz
RS232/RS485 interface (optional) with up to 115200 bit/s and USB 2.0 interface
MODBUS protocol
Auxiliary power supply via internal transformer or universal AC/DC module
Automatische Bereichswahl für Spannungsmessung (max. 600 VL-N)
Housing for DIN rail mounting
User-friendly MiQen software
Nominal values
62,5, 125, 250, 500 VL-N
Nominal voltage UN
500 VL-N
Max. value (continuous)
600 VL-N
Max. Permissible value(according to EN 60688)
2 × UN; 10 s
Input resistance
500 kOhm
Consumption
U2/500 kOhm
Frequency measuring range(only for frequency measurements)
16 ... 400 Hz
The analogue output is fully programmable and can be set to one of the 6 ranges (4 current and 2 voltage ranges) without opening the unit.
Programmable DC current output:Output ranges 0 ... 100%
0 ... 1 mA
Range 1
0 ... 5 mA
Range 2
0 ... 10 mA
Range 3
0/4 ... 20 mA
Range 4
Other ranges
via MiQen software
Max. Voltage level
10 V
Maximum load resistance
RB max =10 V / IoutN
Output ranges 0 ... 100%
0 ... 1 V
0 ... 10 V
Max. load current
20 mA
Min. load resistance
RBmin= UoutN / 10 mA